Endpoint:
flash point of flammable liquids
Type of information:
experimental study
Adequacy of study:
key study
Study period:
January 2010
Reliability:
2 (reliable with restrictions)
Rationale for reliability incl. deficiencies:
comparable to guideline study with acceptable restrictions
Qualifier:
equivalent or similar to guideline
Guideline:
ISO 2719 (Determination of flash point - Pensky-Martens closed cup method)
Version / remarks:
2002
Qualifier:
equivalent or similar to guideline
Guideline:
ASTM D93 (Standard test methods for flash point by pensky-martens closed cup tester)
Version / remarks:
ASTM D93-07
GLP compliance:
no
Other quality assurance:
other: DIN EN ISO 9001
Type of method:
closed cup
Remarks:
MP EN22719A/ ISO2719A
Flash point apparatus:
Pensky-Martens apparatus
Dynamic viscosity of test material:
11.47 mPa*s (20°C)
Key result
Flash point:
117 °C
Atm. press.:
1 013 hPa

Details on single measurements:

First measurement: 117.0 °C;

Second measurement: 117.5 °C;

Mean value: 117 °C

The correction to ambient pressure (1013 hPa) was accomplished automatically during measurements by the apparatus.

Interpretation of results:
GHS criteria not met
Conclusions:
Flash point (ISO 2719 / ASTM D93-07): 117 °C at 1013 hPa
Executive summary:

The flash point for the submission substance was determined according to EU method A.9 using the Pensky-Martens closed cup method according to DIN EN ISO 2719 and ASTM D93-07. Two replicate

measurements were performed, resulting in a mean flash point of 117 °C at 1013 hPa.

The laboratory complied with a quality management system according to DIN EN ISO 9001 : 2008.

Description of key information

Flash point (DIN EN ISO 2719 / ASTM D93 -07): 117 °C at 1013 hPa

Key value for chemical safety assessment

Flash point at 101 325 Pa:
117 °C

Additional information

The flash point for the submission substance was determined according to EU method A.9 using the Pensky-Martens closed cup method according to DIN EN ISO 2719 and ASTM D93-07. Two replicate

measurements were performed, resulting in a mean flash point of 117 °C at 1013 hPa.

The laboratory complied with a quality management system according to DIN EN ISO 9001 : 2008.